NMD90 Aluminum 300 Volts 90°C

 

 

Three ACM aluminum conductors with 90°C XLPE (R90) insulation. Bare bonding wire and overall jacket of moisture resistant and flame retardant PVC, with FT1 rating. Rated 300 volts.

Insulation Colours:  Black, Red, White
CSA Spec C22.2 No. 48-M90

Applications:

ECS
Catalogue
Number
Conductor Bonding Wire AWG Size Insulation
(inches)
Jacket
(inches)

Ampacity

(30°C Ambient)
(amps)

Nominal
O.D.
(inches)
Total
Weight
(lbs/km)
No. AWG
Size
Stranding
NMDA08-03 3 8 Solid 10 .045 .045 30 .610 450
NMDA06-03 3 6 Solid 8 .045 .045 55 .690 656
NMDA04-03 3 4 Solid 6 .045 .060 65 830 967
NMDA03-03 3 3 Solid 6 .045 .080 75 .920 1,230
NMDA02-03 3 2 Solid 6 .045 .080 95 .990 1,410

 

* Ampacity per 310.15 and 334.80, National Electrical Code, 2002 edition.

 

Applications:
For open or concealed wiring in dry or damp locations where not exposed to mechanical injury.
Minimum recommended installation temperature minus 25°C (except for 3 conductor cables at minus 10°C) with suitable handling procedures. Maximum conductor temperature 90°C. Approved for use with ceiling fixtures.